General Information
Weber Packaging Solutions, Inc. 2-3
The Stop feature can be wired in series with other equipment stop facilities,
upstream or downstream of the applicator, and ganged with the system E-Stop.
As stated by EN418, no emergency switch device will be provided as standard
equipment.
See Chapter 9, Appendix for information on installing the optional Stop switch.
! NOTICE ! MINIMUM CREEPAGE DISTANCES AND DOUBLE INSULATION
SPECIFIED IN EN60204 MUST BE PROVIDED WHEN USING
CUSTOMER-SUPPLIED EMERGENCY STOP DEVICE.
! ADVERTISSEMENT ! LA DISTANCE DU RAMPAGE [CREEPAGE] MINIMUME ET LE
DOUBLE-ISOLEMENT QUI EST SpÉCIFIé SELON LA NORME
EN60204 DOIVENT ÊTRE FOURNES LORSQUE LE CLIENT
FOURNIT APPAREIL D’INTERRUPTION D’URGENCE.
! ACHTUNG ! MINIMALE KRIECHSTRECKE UND DOPPELTE ISOLIERUNG
SPEZIFIZIERTE IN EN 60204 MUSS VERFÜGT WERDEN WENN
VERWENDEN DEN KUNDENLIEFERTEN NOTSCHALTER.
Pneumatic Power Supply Failure
It is the responsibility of the equipment installer, integrator, and end user to supply a safety pressure
switch. The safety pressure switch must disengage the pneumatic power supply to the applicator when
pneumatic power is lost, the stop button is pressed, or a door switch tripped. (See Figure 2-1.)