EasyManua.ls Logo

WEG CFW700 - Block Diagram for the CFW700

WEG CFW700
250 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CFW700 | 5
General Instructions
English
Analog
inputs
AI1 and AI2
FLASH
memory
module
(Slot 5)
Digital inputs
DI1 to DI8
Control power supply and interfaces
between power and control
RS-485
PC
POWER
CONTROL
Three-phase
rectifier
C3 RFI filter (*)
(available in
CFW700...C3...
inverters)
Motor
U/T1
V/T2
W/T3
DC+ DC-BR
Inverter
with
IGBT
transistors
Mains power
supply
R/L1/L
S/L2/N
T/L3
= DC bus connection
= Braking resistor
connection
Pre-
charge
WPS software
WLP software
DC link chokes
DC link capacitor bank
Braking IGBT (available in
CFW700...DB... inverters)
RFI filter
Keypad
CC700
Control
board
with a
32 bits
"RISC"
CPU
Analog
outputs
AO1 and AO2
Digital output
DO1 (RL1)
Digital outputs
DO2 to DO5
Keypad
(remote)
Feedback:
- voltage
- current
PE
PE
COMM 1
(Slot 3 - Green)
Accessories
= Keypad (HMI)
(*) The capacitor to the ground of the C3 RFI filter (it is possible to meet the
requirements of category C2 with this filter on mechanics A models) must be
disconnected for IT networks and grounded delta power supplies. Please
refer to item 3.2.3.1 Input Connections on page 15.
Figure 2.1: Block diagram for the CFW700

Table of Contents

Other manuals for WEG CFW700