Energy Counter
Global Parameters of the Impedance Measurement
Parameter Description Setting range Default Menu path
Scaling Z Display of the measured values as primary,
secondary or per unit values.
Note: The Disturbance Recorder and SCADA
always use primary impedance values.
Primary values,
Secondary
values
Secondary
values
[Device Para
/Measurem
Display
/General
Settings]
252 MCDGV4 DOK-HB-MCDGV4-2E