EasyManua.ls Logo

Woodward HighPROTEC - Page 258

Woodward HighPROTEC
1369 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Statistics
Parameter Description Setting range Default Menu path
Start I Demand
Fc
Start of the calculation, if the assigned
signal becomes true.
Only available if: Start I Demand via: =
StartFct
1..n,
Assignment List
-.- [Device Para
/Statistics
/Demand
/Current
Demand]
ResFc I
Demand
Resetting of Statistics - Current Demand
(avg, peak avg)
1..n,
Assignment List
-.- [Device Para
/Statistics
/Demand
/Current
Demand]
Duration I
Demand
Recording time
Only available if: Start I Demand via: =
Duration
2 s,
5 s,
10 s,
15 s,
30 s,
1 min,
5 min,
10 min,
15 min,
30 min,
1 h,
2 h,
6 h,
12 h,
1 d,
2 d,
5 d,
7 d,
10 d,
30 d
15 s [Device Para
/Statistics
/Demand
/Current
Demand]
Window I
Demand
Window configuration sliding,
fixed
sliding [Device Para
/Statistics
/Demand
/Current
Demand]
Start P Demand
via:
Start Active Power demand by: Duration,
StartFct
Duration [Device Para
/Statistics
/Demand
/Power
Demand]
258 MCDGV4 DOK-HB-MCDGV4-2E

Table of Contents