Parameter Description Setting range Default Menu path
Start P Demand
Fc
Start of the calculation, if the assigned
signal becomes true.
Only available if: Start P Demand via: =
StartFct
1..n,
Assignment List
-.- [Device Para
/Statistics
/Demand
/Power
Demand]
ResFc P
Demand
Resetting of Statistics - Power Demand (avg,
peak avg)
1..n,
Assignment List
-.- [Device Para
/Statistics
/Demand
/Power
Demand]
Duration P
Demand
Recording time
Only available if: Start P Demand via: =
Duration
2 s,
5 s,
10 s,
15 s,
30 s,
1 min,
5 min,
10 min,
15 min,
30 min,
1 h,
2 h,
6 h,
12 h,
1 d,
2 d,
5 d,
7 d,
10 d,
30 d
15 s [Device Para
/Statistics
/Demand
/Power
Demand]
Window P
Demand
Window configuration sliding,
fixed
sliding [Device Para
/Statistics
/Demand
/Power
Demand]
259 MCDGV4 DOK-HB-MCDGV4-2E