Protective Elements
Synchrocheck Override Conditions
If enabled the following conditions can override the synchrocheck function:
LBDL = Live Bus – Dead Line
DBLL = Dead Bus – Live Line
DBDL = Dead Bus – Dead Line
Also the synchrocheck function can be bypassed by an external source.
When the synchrocheck function is overridden or bypassed, synchronization
has to be secured by other synchronizing systems before breaker closing!
942 MCDGV4 DOK-HB-MCDGV4-2E