Parameter List
1
1.17 U: Monitors
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 113
No.
(Hex.)
Name Description MFAO Signal Level
U1-10
(0049)
Input Terminal Status
Shows the status of the MFDI terminal where 1 = (ON) and 0 = (OFF).
For example, U1-10 shows “00000011” when terminals S1 and S2 are ON.
bit 0 : Terminal S1 (MFDI 1)
bit 1 : Terminal S2 (MFDI 2)
bit 2 : Terminal S3 (MFDI 3)
bit 3 : Terminal S4 (MFDI 4)
bit 4 : Terminal S5 (MFDI 5)
bit 5 : Terminal S6 (MFDI 6)
bit 6 : Terminal S7 (MFDI 7)
bit 7 : Terminal S8 (MFDI 8)
No signal output available
U1-11
(004A)
Output Terminal Status
Shows the status of the MFDO terminal where 1 = (ON) and 0 = (OFF).
For example, U1-11 shows “00000011” when terminals M1 and M3 are ON.
Note:
When H2-xx = 100 to 19F [Inverse Output of Function], the value before inversion is displayed.
bit 0 : Terminals M1-M2
bit 1 : Terminals M3-M4
bit 2 : Terminals M5-M6
bit 3 : Not used (normal value of 0).
bit 4 : Not used (normal value of 0).
bit 5 : Not used (normal value of 0).
bit 6 : Not used (normal value of 0).
bit 7 : Fault relay MA/MB-MC
No signal output available
U1-12
(004B)
Drive Status
Shows drive status where 1 = (ON) and 0 = (OFF).
For example, U1-12 shows “00000101” during run with the Reverse Run command.
bit 0 : During Run
bit 1 : During zero-speed
bit 2 : During reverse
bit 3 : During fault reset signal input
bit 4 : During speed agreement
bit 5 : Drive ready
bit 6 : During minor fault detection
bit 7 : During fault detection
No signal output available
U1-13
(004E)
Terminal A1 Level
Shows the signal level of terminal A1.
Unit: 0.1%
10 V = 100% (-10 V to +10
V)
U1-14
(004F)
Terminal A2 Level
Shows the signal level of terminal A2.
Unit: 0.1%
10 V = 100% (-10 V to +10
V)
U1-15
(0050)
Terminal A3 Level
Shows the signal level of terminal A3.
Unit: 0.1%
0 V = 100% (-10 V to +10
V)
U1-16
(0053)
SFS Output Frequency
Shows the output frequency after soft start. Shows the frequency with acceleration and deceleration
times and S-curves. Parameter o1-03 [Keypad Display Unit Selection] sets the display units.
Unit: 0.01 Hz
10 V = Maximum frequency
(-10 V to +10 V)
U1-17
(0058)
DI-A3 Input Status
Shows the reference value input from DI-A3 option.
Shows the input signal for DI-A3 in hexadecimal as set in F3-01 [Digital Input Function Selection].
3FFFF: Set (1 bit) + Sign (1 bit) + 16 bit
No signal output available
U1-18
(0061)
oPE Fault Parameter
Shows the parameter number that caused the oPE02 [Parameter Range Setting Error] or oPE08
[Parameter Selection Error].
No signal output available