4.6 Control I/O Connections
632 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
4.6 Control I/O Connections
This section gives information about the settings for the listed control circuit I/O signals.
MFDI (terminals S1 to S8)
Pulse train output (terminal MP)
MFAI (terminals A1 to A3)
PTC input (terminal A3)
MFAO (terminals FM, AM)
MEMOBUS/Modbus communications (terminals D+, D-, AC)
Pulse Train Output
You can use pulse train monitor output terminal MP for sourcing mode or for sinking mode.
Use for sourcing mode
The load impedance changes the voltage level of the pulse train output signal.
Load Impedance
R
L
(kΩ)
Output Voltage
V
MP
(V)
1.5 or more 5 Vor more
4.0 or more 8 Vor more
10 or more 10 Vor more
Note:
Use the formula in Figure 4.28 to calculate the necessary load resistance (kΩ) to increase output voltage V
MP
(V).
A - Load Impedance
Figure 4.28 Wiring to Use Pulse Train Output in Sourcing Mode
Use in sinking mode
The external power supply changes the voltage level of the pulse train output signal. Keep the voltage from an
external source between 10.8 Vdc to 16.5 Vdc. Adjust the load impedance to keep the current at 16 mA or lower.
External Power Supply (V) Load Impedance (kΩ) Sinking current (mA)
10.8 Vdc to 16.5 Vdc 1.0 or more 16 mA maximum
A - External power supply
B - Load Impedance
C - Sinking current
Figure 4.29 Wiring to Use Pulse Train Output in Sinking Mode