1.8 E: Motor Parameters
44 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
1.8 E: Motor Parameters
◆ E1: V/f Pattern for Motor 1
No.
(Hex.)
Name Description
Default
(Range)
Ref.
E1-01
(0300)
Input AC Supply Voltage
Sets the drive input voltage.
NOTICE: Set parameter E1-01 to align with the drive input
voltage (not motor voltage). If this parameter is incorrect, the
protective functions of the drive will not operate correctly and it
can cause damage to the drive.
200 V Class: 240 V, 400
V: 480 V
(200 V Class: 155 to 255
V, 400 V Class: 310 to
510 V)
296
E1-03
(0302)
V/f Pattern Selection
Sets the V/f pattern for the drive and motor. You can use one of the preset patterns or you
can make a custom pattern.
0 : Const Trq, 50Hz base, 50Hz max
1 : Const Trq, 60Hz base, 60Hz max
2 : Const Trq, 50Hz base, 60Hz max
3 : Const Trq, 60Hz base, 72Hz max
4 : VT, 50Hz, 65% Vmid reduction
5 : VT, 50Hz, 50% Vmid reduction
6 : VT, 60 Hz, 65% Vmid reduction
7 : VT, 60Hz, 50% Vmid reduction
8 : High Trq, 50Hz, 25% Vmin boost
9 : High Trq, 50Hz, 65% Vmin boost
A : High Trq, 60Hz, 25% Vmin boost
B : High Trq, 60Hz, 65% Vmin boost
C : High Freq, 60Hz base, 90Hz max
D : High Freq, 60Hz base, 120Hz max
E : High Freq, 60Hz base, 180Hz max
F : Custom
Note:
• When A1-02 = 2 [Control Method Selection = OLV], settings 0 to E are not
available.
• Set the correct V/f pattern for the application and operation area. An incorrect V/f
pattern can decrease motor torque and increase current from overexcitation.
F
(Determined by A1-02)
296
E1-04
(0303)
Maximum Output
Frequency
Sets the maximum output frequency for the V/f pattern.
Determined by A1-02 and
E5-01
(Determined by A1-02
and E5-01)
301
E1-05
(0304)
Maximum Output Voltage
Sets the maximum output voltage for the V/f pattern.
200 V Class: 230.0 V, 400
V: 460.0 V
(200 V Class: 0.0 - 255.0
V, 400 V Class: 0.0 -
510.0 V)
302
E1-06
(0305)
Base Frequency
Sets the base frequency for the V/f pattern.
Determined by A1-02 and
E5-01
(0.0 - E1-04)
302
E1-07
(0306)
Mid Point A Frequency
Sets a middle output frequency for the V/f pattern.
Determined by A1-02
(0.0 - E1-04)
302
E1-08
(0307)
Mid Point A Voltage
Sets a middle output voltage for the V/f pattern.
Determined by A1-02,
C6-01 and o2-04
(200 V Class: 0.0 - 255.0
V,
400 V Class: 0.0 - 510.0
V)
302
E1-09
(0308)
Minimum Output
Frequency
Sets the minimum output frequency for the V/f pattern.
Determined by A1-02 and
E5-01
(Determined by A1-02,
E1-04, and E5-01)
302
E1-10
(0309)
Minimum Output Voltage
Sets the minimum output voltage for the V/f pattern.
Determined by A1-02
(200 V Class: 0.0 to 255.0
V, 400 V Class: 0.0 to
510.0 V)
302
E1-11
(030A)
Expert
Mid Point B Frequency
Sets a middle output frequency for the V/f pattern.
0.0 Hz
(0.0 - E1-04)
302