3.7 Fine Tuning during Test Runs (Adjust the Control Function)
604 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
*3 Refer to the section on C5-xx parameters for more information about speed control (ASR).
*4 The best values for a no-load operation are different than the best values for actual loading operation.
Fine-Tuning Open Loop Vector Control for PM Motors
Table 3.19 Parameters for Fine Tuning the Drive (A1-02 = 5[OLV/PM])
Issue Parameter Number Possible Solutions Default Recommended Setting
Unsatisfactory motor performance
E1-xx parameters, E5-xx
parameters
Check the settings for E1-06,
E1-04 [Base Frequency,
Maximum Output Frequency].
Check the E5-xx and make sure
that all motor data has been set
correctly.
Note:
Do not set E5-05 [PM Motor
Resistance (ohms/phase)] to a
line-to-line resistance value.
Do Auto-Tuning.
- -
Unsatisfactory motor torque and
speed response
n8-55 [Motor to Load Inertia
Ratio]
Adjust to match the load inertia
ratio of the motor and machine.
0 Near the actual load inertia ratio.
n8-45 [Speed Feedback Detection
Gain]
Decrease the setting value in
increments of 0.05.
0.80 -
C4-01 [Torque Compensation
Gain]
Adjust the setting value.
Note:
Setting this value too high can
cause overcompensation and
motor oscillation.
0.00 1.00
Oscillation when the motor
starts.
Motor stalls.
n8-51 [Pull-in Current @ Accel/
Decel]
Increase the setting value in
increments of 5%.
50% -
b2-02 [DC Injection Braking
Current]
b2-03 [DC Inject Braking Time
at Start]
Use DC Injection Braking at start.
Note:
This can cause the motor to
rotate in reverse for
approximately 1/8 of a turn at
start.
b2-02: 50%
b2-03: 0.00 s
b2-02: Adjust as necessary.
b2-03: 0.5 s
n8-55 [Motor to Load Inertia
Ratio]
Increase the setting value.
Note:
When operating a single motor
or with a minimum amount of
inertia, setting this value too
high can cause motor
oscillation.
0 Near the actual load inertia ratio.
There is too much current during
deceleration.
n8-79 [Pull-in Current at
Deceleration]
Set n8-79 < n8-51.
50%
Note:
When n8-79 = 0, the drive will
apply the n8-51 setting to the
pull-in current during
deceleration.
Decrease in increments of 5%.
Stalling or oscillation occurs when
load is applied during constant
speed
n8-47 [Pull-in Current Comp Filter
Time]
Decrease the setting value in
increments of 0.2 s.
5.0 s -
n8-48 [Pull-in/Light Load Id
Current]
Increase the setting value in
increments of 5%.
30% -
n8-55 [Motor to Load Inertia
Ratio]
Increase the setting value.
Note:
When operating a single motor
or with a minimum amount of
inertia, setting this value too
high can cause motor
oscillation.
0 Near the actual load inertia ratio.
Hunting or oscillation
n8-45 [Speed Feedback Detection
Gain]
Increase the setting value in
increments of 0.05.
0.80 -
The drive detects STPo [Motor
Step-Out Detected] fault when the
load is not too high.
E5-09 [PM Back-EMF Vpeak
(mV/(rad/s))]
E5-24 [PM Back-EMF L-L
Vrms (mV/rpm)]
Adjust the setting value.
Examine the motor code on the
motor nameplate or the data
sheet, then set correct values for
E5-09 or E5-24.
*1
Yaskawa motor
Set the motor code from the
motor nameplate.
Motor from another
manufacturer
Set the values from the test
report.
The drive detected stalling or STPo
[Motor Step-Out Detected] at high
speed and maximum output
voltage.
n8-62 [Output Voltage Limit
Level]
Set to a value lower than the actual
input voltage.
200.0 V
400.0 V
-