1.10 H: Terminal Functions
66 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Setting Value Function Description Ref.
7B KEB Ride-Thru 2
Activate (N.O.)
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.O.).
ON : Deceleration during momentary power loss
OFF : Normal operation
379
7C Short Circuit Braking (N.
O.)
Sets operation of Short Circuit Braking (N.O.).
ON : Short Circuit Braking is enabled.
OFF : Normal operation
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this function is available only when you use a PM motor.
380
7D Short Circuit Braking (N.
C.)
Sets operation of Short Circuit Braking (N.C.).
ON : Normal operation
OFF : Short Circuit Braking is enabled.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this function is available only when you use a PM motor.
380
7E Reverse Rotation
Identifier
Sets the rotation direction of the motor when in Simple Closed Loop V/f Control method and F1-21, F1-37 = 0
[Encoder Option Function Selection = A pulse detection], or when in Closed Loop V/f Control method.
ON : Reverse run
OFF : Forward run
380
90 - 97 DWEZ Digital Inputs 1 to
8
Sets digital inputs used with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
380
9F DWEZ Disable
Sets operation of the DriveWorksEZ program saved in the drive.
ON : No
OFF : Yes
Note:
Set A1-07 = 2 [DriveWorksEZ Function Selection = Digital input] to enable this function.
380
101 to 19F Inverse Inputs of 1 to 9F Sets the function of the selected MFDI to operate inversely. To select the function, enter 1xx, where the xx is the
function setting value.
Note:
You cannot use inverse input for all functions. Refer to Table 2.55 for more information.
381
H2: Digital Outputs
No.
(Hex.)
Name Description
Default
(Range)
Ref.
H2-01
(040B)
Term M1-M2 Function
Selection
Sets the function for MFDO terminal M1-M2.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in
through mode.
0
(0 - 1FF)
383
H2-02
(040C)
Term M3-M4 Function
Selection
Sets the function for MFDO terminal M3-M4.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in
through mode.
1
(0 - 1FF)
383
H2-03
(040D)
Term M5-M6 Function
Selection
Sets the function for MFDO terminal M5-M6.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in
through mode.
2
(0 - 1FF)
383
H2-06
(0437)
Watt Hour Output Unit
Selection
Sets the unit for the output signal when H2-01 to H2-03 = 39 [MFDO Function Selection
= Watt Hour Pulse Output].
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
0
(0 - 4)
384
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV