Parameter Details
2
2.8 H: Terminal Functions
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 405
A - H2-30
[Comparator 2 On-Delay Time]
B - H2-31
[Comparator 2 Off-Delay Time]
Figure 2.102 Comparator 2 Output Time Chart
Note:
The drive compares the monitors set with H2-26 as absolute values.
■ 69: External Power 24V Supply
Setting Value Function Description
69 External Power 24V Supply
The terminal activates when there is an external 24V power supply between terminals PS-AC.
ON : An external 24V power supply supplies power.
OFF : An external 24V power supply does not supply power.
■ 6A: Data Logger Error
Setting Value Function Description
6A Data Logger Error
The terminal activates when the drive detects LoG [Com Error / Abnormal SD card].
■ 90 to 93: DWEZ Digital Outputs 1 to 4
Setting Value Function Description
90 to 93 DWEZ Digital Outputs 1 to
4
Sets the DriveWorksEZ digital output. Refer to the DriveWorksEZ online manual for more information.
■ A0 to A7: DWEZ Extended Digital Output 1 to 8
Setting Value Function Description
A0 to A7 DWEZ Extended Digital
Outputs 1 to 8
Sets the digital output for the DriveWorksEZ DO-A3 option card. Refer to the DriveWorksEZ online manual for more information.
■ 100 to 1A7: Inverse Outputs of 0 to A7
Setting Value Function Description
100 to 1A7 Inverse Outputs of 0 to A7
Causes inverse output of the function for the selected MFDO. Uses the last two digits of 1xx to select which function to inversely
output.
For example, set H2-xx = 10E for the inverse output of E [Fault].