Parameter List
1
1.10 H: Terminal Functions
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 73
Setting Value Function Description Ref.
62 Modbus Reg 1 Status
Satisfied
The terminal activates when the bit specified by H2-08 [Modbus Register 1 Bit Select] for the MEMOBUS register
address set with H2-07 [Modbus Register 1 Address Select] activates.
403
63 Modbus Reg 2 Status
Satisfied
The terminal activates when the bit specified by H2-10 [Modbus Register 2 Bit Select] for the MEMOBUS register
address set with H2-09 [Modbus Register 2 Address Select] activates.
403
65 Standby Output
The terminal deactivates after the drive stops operating and after the time set with b8-51 [Standby Mode Wait Time].
ON : The Run command turns on and the magnetic contactor on the input side turns on.
OFF : The Run command turns off and the drive stops operating. Then, the magnetic contactor on the input side turns
off after the time set in b8-51 [Standby Mode Wait Time] elapses.
403
66 Comparator1
The terminal activates if the monitor value set with H2-20 [Comparator 1 Monitor Selection] is in range of the values
of H2-21 [Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit] for the time set in H2-24 [Comparator
1 On-Delay Time].
404
67 Comparator2
The terminal activates if the monitor value set with H2-26 [Comparator 2 Monitor Selection] is not in the range of the
values of H2-27 [Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit] for the time set in H2-30
[Comparator 2 On-Delay Time].
404
69 External Power 24V
Supply
The terminal activates when there is an external 24V power supply between terminals PS-AC.
ON : An external 24V power supply supplies power.
OFF : An external 24V power supply does not supply power.
405
6A Data Logger Error
The terminal activates when the drive detects LoG [Com Error / Abnormal SD card].
405
90 to 93 DWEZ Digital Outputs 1
to 4
Sets the DriveWorksEZ digital output. Refer to the DriveWorksEZ online manual for more information.
405
A0 to A7 DWEZ Extended Digital
Outputs 1 to 8
Sets the digital output for the DriveWorksEZ DO-A3 option card. Refer to the DriveWorksEZ online manual for more
information.
405
100 to 1A7 Inverse Outputs of 0 to
A7
Causes inverse output of the function for the selected MFDO. Uses the last two digits of 1xx to select which function
to inversely output.
405
◆ H3: Analog Inputs
No.
(Hex.)
Name Description
Default
(Range)
Ref.
H3-01
(0410)
Terminal A1 Signal Level
Select
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
0
(0 - 3)
408
H3-02
(0434)
Terminal A1 Function
Selection
Sets the function for MFAI terminal A1.
0
(0 - 32)
408
H3-03
(0411)
RUN
Terminal A1 Gain Setting
Sets the gain of the analog signal input to MFAI terminal A1.
100.0%
(-999.9 - +999.9%)
408
H3-04
(0412)
RUN
Terminal A1 Bias Setting
Sets the bias of the analog signal input to MFAI terminal A1.
0.0%
(-999.9 - +999.9%)
409
H3-05
(0413)
Terminal A3 Signal Level
Select
Sets the input signal level for MFAI terminal A3.
0 : 0 to 10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
0
(0 - 3)
409
H3-06
(0414)
Terminal A3 Function
Selection
Sets the function for MFAI terminal A3.
2
(0 - 32)
409