2.8 H: Terminal Functions
390 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
■ H2-67: Terminal M5-M6 Logical Operation
No.
(Hex.)
Name Description
Default
(Range)
H2-67
(1B4D)
Expert
Terminal M5-M6 Logical
Operation
Sets the logical operation for the functions set in H2-03 [Term M5-M6 Function Selection] and H2-
66 [Term M5-M6 Secondary Function].
0
(0 - 8)
Note:
Refer to Output of Logical Operation Results of MFDO on page 382 for more information about the relation between parameter settings and
logical operations.
■ H2-68: Terminal M5-M6 Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-68
(1B4E)
Expert
Terminal M5-M6 Delay
Time
Sets the minimum on time used to output the logical calculation results from terminal M5-M6.
0.1 s
(0.0 - 25.0 s)
◆ MFDO Setting Value
Selects the function configured to a MFDO.
■ 0: During Run
Setting Value Function Description
0 During Run
The terminal activates when the Run command is input and when the drive is outputting voltage.
Figure 2.89 Drive Running Time Chart
ON : Drive is running
The drive is receiving a Run command or outputting voltage.
OFF : Drive is stopping
Drive is stopped.
■ 1: Zero Speed
Setting Value Function Description
1 Zero Speed
The terminal activates when the output frequency < E1-09 [Minimum Output Frequency] or b2-01 [DC Injection/Zero
SpeedThreshold].