■ H2-60: Term M1-M2 Secondary Function
No.
(Hex.)
Name Description
Default
(Range)
H2-60
(1B46)
Expert
Term M1-M2 Secondary
Function
Sets the second function for terminal M1-M2. Outputs the logical calculation results of the terminals
assigned to functions by H2-01 [Term M1-M2 Function Selection].
F
(0 - FF)
■ H2-61: Terminal M1-M2 Logical Operation
No.
(Hex.)
Name Description
Default
(Range)
H2-61
(1B47)
Expert
Terminal M1-M2 Logical
Operation
Sets the logical operation for the functions set in H2-01 [Term M1-M2 Function Selection] and H2-
60 [Term M1-M2 Secondary Function].
0
(0 - 8)
Note:
Refer to Output of Logical Operation Results of MFDO on page 382 for more information about the relation between parameter settings and
logical operations.
■ H2-62: Terminal M1-M2 Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-62
(1B48)
Expert
Terminal M1-M2 Delay
Time
Sets the minimum on time used to output the logical calculation results from terminal M1-M2.
0.1 s
(0.0 - 25.0 s)
■ H2-63: Term M3-M4 Secondary Function
No.
(Hex.)
Name Description
Default
(Range)
H2-63
(1B49)
Expert
Term M3-M4 Secondary
Function
Sets the second function for terminal M3-M4. Outputs the logical calculation results of the terminals
assigned to functions by H2-02 [Term M3-M4 Function Selection].
F
(0 - FF)
■ H2-64: Terminal M3-M4 Logical Operation
No.
(Hex.)
Name Description
Default
(Range)
H2-64
(1B4A)
Expert
Terminal M3-M4 Logical
Operation
Sets the logical operation for the functions set in H2-02 [Term M3-M4 Function Selection] and H2-
63 [Term M3-M4 Secondary Function].
0
(0 - 8)
Note:
Refer to Output of Logical Operation Results of MFDO on page 382 for more information about the relation between parameter settings and
logical operations.
■ H2-65: Terminal M3-M4 Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-65
(1B4B)
Expert
Terminal M3-M4 Delay
Time
Sets the minimum on time used to output the logical calculation results from terminal M3-M4.
0.1 s
(0.0 - 25.0 s)
■ H2-66: Term M5-M6 Secondary Function
No.
(Hex.)
Name Description
Default
(Range)
H2-66
(1B4C)
Expert
Term M5-M6 Secondary
Function
Sets the second function for terminal M5-M6. Outputs the logical calculation results of the terminals
assigned to functions by H2-03 [Terminal M5-M6 Function Select].
F
(0 - FF)