Keypad Use and Test Run
3
3.7 Fine Tuning during Test Runs (Adjust the Control Function)
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 601
*4 Recommended settings are for 200 V class drives. Multiply the voltage by 2 for 400 V class drives.
*5 In Closed Loop V/f Control, ASR only controls the output frequency. You cannot make a high-gain as in Closed Loop Vector control.
Open Loop Vector Control Method
In Open Loop Vector Control, keep C4-01 [Torque Compensation Gain] at its default setting (1.00).
If you cannot get speed precision during regeneration in Open Loop Vector Control, set C3-04 = 1 [Slip
Compensation @ Regen Select = Enabled above 6 Hz].
Table 3.16 Parameters for Fine Tuning the Drive (A1-02 = 2[OLV])
Issue Parameter Number Possible Solutions Default Recommended Setting
Unsatisfactory motor torque
and speed response
Hunting or oscillation at mid-
range speeds (10 Hz to 40 Hz)
n2-01 [SpdFeedbackDetectCtr
(AFR) Gain]
To increase the speed of torque
or speed response, decrease the
setting value in increments of
0.05.
If hunting or oscillation occur,
decrease the setting value in
increments of 0.05.
1.00 0.50 - 2.00
n2-02 [SpdFeedbackDetCtr(AFR)
TimeConst1]
To increase the speed of torque
or speed response, decrease the
setting value in increments of
10 ms and examine the
response.
If hunting or oscillation occur
or if the load inertia is too
much, increase the setting value
in increments of 50 ms and
examine the response.
Note:
Make sure that this parameter
setting is: n2-02 n2-03
[Automatic Freq Regulator
Time 2] holds true.
When you adjust n2-02, you
must also increase the C4-02
[Motor 1 Torque Comp Delay
Time] value by the same ratio.
50 ms 50 ms to 2000 ms
ov [overvoltage] occurs when the
drive stops accelerating, starts to
decelerate, or when there are large
changes in the load.
n2-03 [SpdFeedbackDetCtr(AFR)
TimeConst2]
If ov occurs, increase the setting
value in increments of 50 ms
and examine the response.
If the response is not sufficient,
decrease the setting value in
increments of 10 ms and
examine the response.
Note:
Make sure that this parameter
setting is: n2-02 [Automatic
Freq Regulator Time 1] n2-
03. When you adjust n2-03 you
must also increase the C4-06
[Motor 2 Torque Comp Delay
Time] value by the same ratio.
750 ms 750 ms to 2000 ms
C4-06 [Motor 2 Torque Comp
Delay Time]
If ov occurs, increase the setting
value in increments of 10 ms
and examine the response.
If the response is not sufficient,
decrease the setting value in
increments of 2 ms and
examine the response.
Note:
Make sure that this parameter
setting is: C4-02 [Torque
Compensation Delay Time]
C4-06.
When you adjust C4-06, you
must also increase the n2-03
[SpdFeedbackDetCtr(AFR)
TimeConst2] value by the same
ratio.
150 ms 150 ms to 750 ms