Parameter Details
2
2.6 E: Motor Parameters
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 303
E1-12: Mid Point B Voltage
No.
(Hex.)
Name Description
Default
(Range)
E1-12
(030B)
Expert
Mid Point B Voltage
Sets a middle point voltage for the V/f pattern.
0.0 V
(200 V Class: 0.0 to 255.0 V,
400 V Class: 0.0 to 510.0 V)
Note:
Set this parameter to 0.0 to disable the function.
E1-13: Base Voltage
No.
(Hex.)
Name Description
Default
(Range)
E1-13
(030C)
Expert
Base Voltage
Sets the base voltage for the V/f pattern.
0.0 V
(200 V Class: 0.0 - 255.0
V,400 V Class: 0.0 - 510.0
V)
Note:
After Auto-Tuning, the value of E1-13 = E1-05 [Maximum Output Voltage].
When E1-13 = 0.0, use the value of E1-05 to control the voltage.
E2: Motor Parameters
E2 parameters [Motor Parameters] are used to set induction motor data. To switch drive operation from one motor to
another motor, configure the first motor (motor 1).
Performing Auto-Tuning automatically sets the E2 parameters to the optimal values. If Auto-Tuning cannot be
performed, set the E2 parameters manually.
Note:
If A1-02 [Control Method Selection] is set to the following control modes, the keypad does not display E2-xx.
5 [PM Open Loop Vector]
6 [PM Advanced Open Loop Vector]
7 [PM Closed Loop Vector]
8 [EZ Vector Control]
E2-01: Motor Rated Current (FLA)
No.
(Hex.)
Name Description
Default
(Range)
E2-01
(030E)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by o2-04, C6-01
(10% to 200% of the drive
rated current)
Note:
If E2-01 < E2-03 [Motor No-Load Current], the drive will detect oPE02 [Parameter Range Setting Error].
When the drive model changes, the display units for this parameter also change.
0.01 A: models 2004 to 2042, 4002 to 4023
0.1 A: models 2056 to 2415, 4031 to 4720
The value set for E2-01 becomes the reference value for motor protection, the torque limit, and torque control. Enter
the motor rated current shown on the motor nameplate. Auto-Tuning the drive will automatically set E2-01 to the
value input for Motor Rated Current.
E2-02: Motor Rated Slip
No.
(Hex.)
Name Description
Default
(Range)
E2-02
(030F)
Motor Rated Slip
Sets motor rated slip.
Determined by o2-04, C6-01
(0.000 - 20.000 Hz)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents