2.6 E: Motor Parameters
302 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
■ E1-05: Maximum Output Voltage
No.
(Hex.)
Name Description
Default
(Range)
E1-05
(0304)
Maximum Output Voltage
Sets the maximum output voltage for the V/f pattern.
200 V Class: 230.0 V, 400 V:
460.0 V
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
■ E1-06: Base Frequency
No.
(Hex.)
Name Description
Default
(Range)
E1-06
(0305)
Base Frequency
Sets the base frequency for the V/f pattern.
Determined by A1-02 and
E5-01
(0.0 - E1-04)
■ E1-07: Mid Point A Frequency
No.
(Hex.)
Name Description
Default
(Range)
E1-07
(0306)
Mid Point A Frequency
Sets a middle output frequency for the V/f pattern.
Determined by A1-02
(0.0 - E1-04)
■ E1-08: Mid Point A Voltage
No.
(Hex.)
Name Description
Default
(Range)
E1-08
(0307)
Mid Point A Voltage
Sets a middle output voltage for the V/f pattern.
Determined by A1-02,C6-
01 and o2-04
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
Note:
Default setting is determined by A1-02 [Control Method Selection], C6-01 [Normal / Heavy Duty Selection], and o2-04 [Drive Model
Selection].
■ E1-09: Minimum Output Frequency
No.
(Hex.)
Name Description
Default
(Range)
E1-09
(0308)
Minimum Output Frequency
Sets the minimum output frequency for the V/f pattern.
Determined by A1-02 and
E5-01
(Determined by A1-02, E1-
04, and E5-01)
■ E1-10: Minimum Output Voltage
No.
(Hex.)
Name Description
Default
(Range)
E1-10
(0309)
Minimum Output Voltage
Sets the minimum output voltage for the V/f pattern.
Determined by A1-02
(200 V Class: 0.0 to 255.0 V,
400 V Class: 0.0 to 510.0 V)
■ E1-11: Mid Point B Frequency
No.
(Hex.)
Name Description
Default
(Range)
E1-11
(030A)
Expert
Mid Point B Frequency
Sets a middle output frequency for the V/f pattern.
0.0 Hz
(0.0 - E1-04)
Note:
Set this parameter to 0.0 to disable the function.