Parameter List
1
1.20 Parameters Changed by E1-03 [V/f Pattern Selection]
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 131
1.20 Parameters Changed by E1-03 [V/f Pattern Selection]
The values for parameters A1-02 [Control Method Selection] and E1-03 [V/f Pattern Selection] changes the default
settings for the parameters in these tables:
Table 1.1 Parameters Changed by E1-03 (2004 to 2021 and 4002 to 4012)
No.
Unit
Setting Value Control Method (A1-02 Setting)
E1-
03
0 1 2 3 4 5 6 7 8 9 A B C D E F
OLV
(2)
CLV
(3)
OLV/
PM
(5)
AOL-
V/PM
(6)
CLV/
PM
(7)
E1-04 Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 180.0
60.0
*1
60.0 60.0
*2 *2 *2
E1-05
*3
V 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0
230.0
*1
230.0 230.0
*2 *2 *2
E1-06 Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0
60.0
*1
60.0 60.0
*2 *2 *2
E1-07 Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0
3.0
*1
3.0 0.0 - - -
E1-08
*3
V 17.3 17.3 17.3 17.3 40.3 57.5 40.3 57.5 21.9 27.6 21.9 27.6 17.3 17.3 17.3
17.3
*1
13.8 0.0 - - -
E1-09 Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5
1.5
*1
0.5 0.0
*2 *2
0.0
E1-10
*3
V 10.4 10.4 10.4 10.4 9.2 10.4 9.2 10.4 12.7 15.0 12.7 17.3 10.4 10.4 10.4
10.2
*1
2.9 0.0 - - -
*1 These values are the default settings for E1-04 to E1-10 and E3-04 to E3-10 [V/f Pattern for Motor 2]. These settings are the same as
those for the V/f pattern when E1-03 = 1 [Const Trq, 60Hz base, 60Hz max].
*2 The default setting varies depending on the setting of E5-01 [PM Motor Code Selection].
*3 This is the value for 200 V class drives. Double the value for 400 V class drives.
Table 1.2 Parameters Changed by E1-03 (2030 to 2211 and 4018 to 4103)
No.
Unit
Setting Value Control Method (A1-02 Setting)
E1-
03
0 1 2 3 4 5 6 7 8 9 A B C D E F
OLV
(2)
CLV
(3)
OLV/
PM
(5)
AOL-
V/PM
(6)
CLV/
PM
(7)
E1-04 Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 180.0
60.0
*1
60.0 60.0
*2 *2 *2
E1-05
*3
V 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0 230.0
230.0
*1
230.0 230.0
*2 *2 *2
E1-06 Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0
60.0
*1
60.0 60.0
*2 *2 *2
E1-07 Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0
3.0
*1
3.0 0.0 - - -
E1-08
*3
V 16.1 16.1 16.1 16.1 40.3 57.5 40.3 57.5 20.7 26.5 20.7 26.5 16.1 16.1 16.1
16.1
*1
12.7 0.0 - - -
E1-09 Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5
1.5
*1
0.5 0.0
*2 *2
0.0
E1-10
*3
V 8.1 8.1 8.1 8.1 6.9 8.1 6.9 8.1 10.4 12.7 10.4 15.0 8.1 8.1 8.1
8.1
*1
2.3 0.0 - - -
*1 These values are the default settings for E1-04 to E1-10 and E3-04 to E3-10 [V/f Pattern for Motor 2]. These settings are the same as
those for the V/f pattern when E1-03 = 1 [Const Trq, 60Hz base, 60Hz max].
*2 The default setting varies depending on the setting of E5-01 [PM Motor Code Selection].
*3 This is the value for 200 V class drives. Double the value for 400 V class drives.