Parameter Details
2
2.11 o: Keypad-Related Settings
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 517
■ o1-51: Trend Plot Time Scale Setting
No.
(Hex.)
Name Description
Default
(Range)
o1-51
(11CB)
RUN
Trend Plot Time Scale
Setting
Sets the time scale (horizontal axis) to display the trend plot. When you change this setting, the drive
automatically adjusts the data sampling time. This parameter is only available when using an LCD
keypad.
300 s
(1 - 3600 s)
■ o1-55: Analog Gauge Area Selection
No.
(Hex.)
Name Description
Default
(Range)
o1-55
(11EE)
RUN
Analog Gauge Area
Selection
Sets the range used to display the monitor set in o1-24 [Custom Monitor 1] as an analog gauge. This
parameter is only available when using an LCD keypad.
1
(0, 1)
0 : +/- Area ( - o1-56 ~ o1-56 )
1 : + Area ( 0 ~ o1-56 )
■ o1-56: Analog Gauge Area Setting
No.
(Hex.)
Name Description
Default
(Range)
o1-56
(11EF)
RUN
Analog Gauge Area Setting
Sets the value used to display the monitor set in o1-24 [Custom Monitor 1] as an analog meter. This
parameter is only available when using an LCD keypad.
100.0%
(0.0 - 100.0%)
■ o1-58: Motor Power Unit Selection
No.
(Hex.)
Name Description
Default
(Range)
o1-58
(3125)
Motor Power Unit Selection
Sets the setting unit for parameters that set the motor rated power.
1
(0, 1)
The drive shows these parameter values in the set units:
• E2-11 [Motor Rated Power]
• E4-11 [Motor 2 Rated Power]
• E5-02 [PM Motor Rated Power]
• E9-07 [Motor Rated Power]
• T1-02 [Motor Rated Power]
• T2-04 [PM Motor Rated Power]
• T4-08 [Motor Rated Capacity]
0 : kW
Shows the motor output in kW units.
1 : HP
Shows the motor output in HP units.
◆ o2: Keypad Operation
■ o2-01: LO/RE Key Function Selection
No.
(Hex.)
Name Description
Default
(Range)
o2-01
(0505)
LO/RE Key Function
Selection
Sets the function that lets you use to switch between LOCAL and REMOTE Modes.
1
(0, 1)
0 : Disabled