3.5 Auto-Tuning
590 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Table 3.5 Input Data for Induction Motor Auto-Tuning
Input Data Parameter Unit
Auto-Tuning Mode
(T1-01 Setting)
Rotational Auto-Tuning
(0)
Stationary Auto-Tuning
1
(1)
Line-to-Line Resistance
(2)
Motor Rated Power T1-02 kW x x x
Motor Rated Voltage T1-03 V x x -
Motor Rated Current T1-04 A x x x
Motor Base Frequency T1-05 Hz x x -
Number of Motor Poles T1-06 - x x -
Motor Base Speed T1-07 min
-1
x x -
Encoder Pulse Count (PPR) T1-08 -
*1
*1
-
Motor No-Load Current T1-09 A - x -
Motor Rated Slip Frequency
T1-10 Hz -
*2
-
Motor Iron Loss
T1-11 W
*3
- -
Test Mode Selection
*4
T1-12 - -
*5
-
No-load voltage
T1-13 V
*6
*6
-
*1 Input this value when A1-02 = 3 [Control Method Selection = Closed Loop Vector].
*2 Shows 0 Hz as the default value. If you do not know the Motor Rated Slip Frequency, keep the setting at 0 Hz.
*3 Input this value when A1-02 = 0 or 1 [Control Method Selection = V/f Control or V/f Control w/ PG].
*4 If T1-12 = 1 [Test Mode Selection = Yes], when you run the motor in Drive Mode for the first time after Auto-Tuning, the drive will
automatically set E2-02 [Motor Rated Slip] and E2-03 [Motor No-Load Current].
*5 Input this value when T1-10 [Motor Rated Slip Frequency] = 0 Hz.
*6 Set the same value to No-Load Voltage as T1-03 [Motor Rated Voltage] to get the same characteristics using Yaskawa 1000-Series drives
or other legacy models.
Auto-Tuning for Motor Parameters for PM Motor
This section gives information about Auto-Tuning for PM motors. Auto-Tuning sets these parameters:
Motor parameters E1-xx, E5-xx
Speed feedback detection uses F1-xx (only with CLV/PM)
Table 3.6 Auto-Tuning for PM Motors
Mode Parameter Settings Application Conditions and Benefits
Applicable Control Method
(A1-02 Setting)
OLV/PM
(5)
AOLV/PM
(6)
CLV/PM
(7)
PM Motor Parameter Settings T2-01 = 0
When the information from the motor test report or
motor nameplate is available.
Rotational/Stationary Auto-Tuning that energizes the
motor is not done. Manually input the necessary
motor parameters.
x x x
PM Stationary Auto-Tuning T2-01 = 1
When the information from the motor test report or
motor nameplate is not available.
Note:
With Stationary Auto-Tuning, the energized drive
stays stopped for approximately 1 minute. During
this time, the drive automatically measures the
necessary motor parameters.
x x x
PM Stationary Auto-Tuning for
Stator Resistance
T2-01 = 2
After Auto-Tuning, the wiring distance between the
drive and motor changed by 50 m or more.
When the motor output and drive capacity are
different.
x x x