Mechanical & Electrical Installation
4
4.5 Control Circuit Wiring
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 631
4. Install the LED status ring board, front cover, and the keypad to their initial positions.
Switches and Jumpers on the Terminal Board
The terminal board has switches to adapt the drive I/Os to the external control signals as shown in Figure 4.27.
Set the switches to select the functions for each terminal.
Figure 4.27 Locations of Switches
Table 4.10 I/O Terminals and Switches Functions
Posi-
tion
Switch Terminal Function Default Setting
A DIP switch S2 -
Enables and disables the MEMOBUS/Modbus communications
termination resistor.
OFF
B Jumper switch S5 FM, AM Sets terminals FM and AM to voltage or current output.
FM: V (voltage output)
AM: V (voltage output)
C
DIP switch S1-1 A1 Selects the input signal type (voltage/current). V (voltage input)
DIP switch S1-2 A2 Selects the input signal type (voltage/current). I (current input)
DIP switch S1-3 A3 Selects the input signal type (voltage/current). V (voltage input)
D Dip switch S4 A3 Selects MFAI or PTC input. AI (analog input)

Table of Contents