1.21 Defaults by Drive Model and Duty Rating ND/HD
140 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
No. Name Unit Default
- Drive Model - 2257 2313 2360 2415
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 75 76 77 78
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP (kW)
75
(55)
100
(75)
100
(75)
125
(90)
125
(90)
150
(110)
150
(110)
150
(110)
L8-09
Output Ground
Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 2 2 2 2 2 2 2 2
n1-03
Hunting
Prevention
Time Constant
ms 10 10 10 10 100 100 100 100
n5-02
Motor Inertia
Acceleration
Time
s 0.317 0.533 0.533 0.592 0.592 0.646 0.646 0.646
*1 Parameters within parentheses are for motor 2.
◆ 400 V Class
No. Name Unit Default
- Drive Model - 4002 4004 4005 4007
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 92 93 94 95
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP (kW)
0.75
(0.4)
1
(0.75)
1.5
(1.1)
2
(1.5)
2
(1.5)
3
(2.2)
3
(2.2)
4
(3.0)
b3-04
V/f Gain
during Speed
Search
% 100 100 100 100 100 100 100 100
b3-06
Speed
Estimation
Current Level
1
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Speed
Estimation
ACR P Gain
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-26
Direction
Determination
Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
Energy Saving
Filter Time
s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
b8-04
Energy Saving
Coefficient
Value
- 576.4 447.4 447.4 338.8 338.8 313.6 313.6 265.7
C5-17
(C5-37)
Motor Inertia kgm
2
0.0015 0.0028 0.0028 0.0068 0.0068 0.0088 0.0088 0.0158
C6-02
Carrier
Frequency
Selection
- 1 7 1 7 1 7 1 7
E2-01
(E4-01)
Motor Rated
Current (FLA)
A 1 1.6 1.6 3.1 3.1 4.2 4.2 5.7