Parameter List
1
1.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 141
No. Name Unit Default
- Drive Model - 4002 4004 4005 4007
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 92 93 94 95
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP (kW)
0.75
(0.4)
1
(0.75)
1.5
(1.1)
2
(1.5)
2
(1.5)
3
(2.2)
3
(2.2)
4
(3.0)
E2-02
(E4-02)
Motor Rated
Slip
Hz 2.9 2.6 2.6 2.5 2.5 3 3 2.7
E2-03
(E4-03)
Motor No-
Load Current
A 0.6 0.8 0.8 1.4 1.4 1.5 1.5 1.9
E2-05
(E4-05)
Motor Line-to-
Line
Resistance
Ω 38.198 22.459 22.459 10.1 10.1 6.495 6.495 4.360
E2-06
(E4-06)
Motor
Leakage
Inductance
% 18.2 14.3 14.3 18.3 18.3 18.7 18.7 19
E2-10
(E4-10)
Motor Iron
Loss
W 14 26 26 53 53 77 77 105
E5-01
PM Motor
Code Selection
- FFFF FFFF FFFF FFFF FFFF FFFF FFFF FFFF
L2-02
Power Loss
Ride Through
Time
s 0.1 0.1 0.2 0.2 0.3 0.3 0.5 0.5
L2-03
Minimum
Baseblock
Time
s 0.2 0.3 0.3 0.4 0.4 0.5 0.5 0.5
L2-04
Powerloss V/f
Recovery
Ramp Time
s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
L2-05
Undervoltage
Detection Lvl
(Uv1)
- 380 380 380 380 380 380 380 380
L3-24
Motor Accel
Time for
Inertia Cal
s 0.178 0.142 0.142 0.166 0.166 0.145 0.145 0.145
L8-02
Overheat
Alarm Level
°C 100 100 105 105 112 112 100 100
L8-09
Output Ground
Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 1 1 1 1 1 1 1 1
n1-03
Hunting
Prevention
Time Constant
ms 10 10 10 10 10 10 10 10
n5-02
Motor Inertia
Acceleration
Time
s 0.178 0.142 0.142 0.166 0.166 0.145 0.145 0.145
*1 Parameters within parentheses are for motor 2.