2.10 n: Special Adjustment
498 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
n7: EZ Drive
The n7 parameters provide special adjustments for EZ Vector Control.
n7-01: Damping Gain for Low Frequency
No.
(Hex.)
Name Description
Default
(Range)
n7-01
(3111)
Expert
Damping Gain for Low
Frequency
Sets the oscillation suppression gain for the low speed range.
1.0
(0.1 - 10.0)
Note:
If oscillation occurs in the low speed range, increase the acceleration time or increase the setting value in 0.5-unit increments.
To get starting torque with the setting for C4-01 [Torque Compensation Gain], decrease the setting value in 0.3-unit increments.
n7-05: Response Gain for Load Changes
No.
(Hex.)
Name Description
Default
(Range)
n7-05
(3115)
Expert
Response Gain for Load
Changes
Sets the response gain related to changes in the load.
100
(10 - 1000)
Note:
To make tracking related to load changes better, increase the setting value in 5-unit increments. If oscillation occurs during load changes,
decrease the setting value in 5-unit increments.
n7-07: Speed Calculation Gain1
No.
(Hex.)
Name Description
Default
(Range)
n7-07
(3117)
Expert
Speed Calculation Gain1
Sets the speed calculation gain during usual operation. Usually it is not necessary to change this
setting.
15.0 Hz
(1.0 - 50.0 Hz)
n7-08: Speed Calculation Gain2
No.
(Hex.)
Name Description
Default
(Range)
n7-08
(3118)
Expert
Speed Calculation Gain2
Sets the speed calculation gain during a speed search.
25.0 Hz
(1.0 - 50.0 Hz)
Note:
When you increase the setting value, you can do a speed search of a motor rotating at a high frequency. If the setting value is too high, the
calculated speed will oscillate and a restart will fail. Decrease the setting value in these conditions.
n7-10: Pull-in Current Switching Speed
No.
(Hex.)
Name Description
Default
(Range)
n7-10
(311A)
Expert
Pull-in Current Switching
Speed
Parameter n8-51 [Pull-in Current @ Acceleration], is in effect when the output frequency is n7-10,
where the speed is set as a percentage of rated speed.
10.0%
(0.0 - 100.0%)
Note:
The value set in n8-51 [Pull-in Current @ Acceleration is enabled for speeds that are not higher than n7-10 during deceleration. The value
set in b8-01 [Energy Saving Control Selection] is enabled for speeds higher than n7-10.
If there is a large quantity of oscillation when you operate in the low speed range, increase the setting value.
When it is most important to save energy in the low speed range, decrease the setting value.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV