Parameter List
1
1.17 U: Monitors
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 115
No.
(Hex.)
Name Description MFAO Signal Level
U2-05
(0084)
Output Current@Fault
Shows the output current at the fault that occurred most recently.
Use U1-03 [Output Current] to monitor the actual output current. The keypad shows the value of U1-
03 in amperes (A).
When looking at the monitor through MEMOBUS/Modbus communications, the current is “8192 =
drive rated current (A)”. Calculate the current from the monitor value that is in at MEMOBUS/
Modbus communications using “Numerals being displayed / 8192 × drive rated current (A)”.
Unit: Determined by the drive model.
• 0.01 A: 2004 to 2042, 4002 to 4023
• 0.1 A: 2056 to 2415, 4031 to 4720
No signal output available
U2-06
(0085)
Motor Speed @ Fault
Shows the motor speed at the fault that occurred most recently.
Use U1-05 [Motor Speed] to monitor the actual motor speed.
Unit: 0.01 Hz
No signal output available
U2-07
(0086)
Output Voltage@Fault
Shows the output voltage reference at the fault that occurred most recently.
Use U1-06 [Output Voltage Ref] to monitor the actual output voltage reference.
Unit: 0.1 V
No signal output available
U2-08
(0087)
DC Bus Voltage@Fault
Shows the DC bus voltage at the fault that occurred most recently.
Use U1-07 [DC Bus Voltage] to monitor the actual DC bus voltage.
Unit: 1 V
No signal output available
U2-09
(0088)
Output Power @ Fault
Shows the output power at the fault that occurred most recently.
Use U1-08 [Output Power] to monitor the actual output power.
Unit: 0.1 kW
No signal output available
U2-10
(0089)
Torque Ref @ Fault
Shows the torque reference at the fault that occurred most recently as a percentage of the motor rated
torque.
Use U1-09 [Torque Reference] to monitor the actual torque reference.
Unit: 0.1%
No signal output available
U2-11
(008A)
Input Terminal Status @
Fault
Shows the status of the MFDI terminals at the most recent fault where 1 = (ON) and 0 = (OFF).
For example, U2-11 shows “00000011” when terminals S1 and S2 are ON.
Use U1-10 [Input Terminal Status] to monitor the actual MFDI terminal status.
bit 0 : Terminal S1
bit 1 : Terminal S2
bit 2 : Terminal S3
bit 3 : Terminal S4
bit 4 : Terminal S5
bit 5 : Terminal S6
bit 6 : Terminal S7
bit 7 : Terminal S8
No signal output available
U2-12
(008B)
Output Terminal Status @
Fault
Shows the status of the MFDO terminals at the most recent fault where 1 = (ON) and 0 = (OFF).
For example, U2-12 shows “00000011” when terminals M1 and M3 are ON.
Use U1-11 [Output Terminal Status] to monitor the actual MFDO terminal status.
bit 0 : Terminals M1-M2
bit 1 : Terminals M3-M4
bit 2 : Terminals M5-M6
bit 3 : Not used (normal value of 0).
bit 4 : Not used (normal value of 0).
bit 5 : Not used (normal value of 0).
bit 6 : Not used (normal value of 0).
bit 7 : Fault relay MA/MB-MC
No signal output available