2.5 d: References
284 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Figure 2.64 Up/Down 2 Example with Reference from Keypad and d4-01 = 1
Up/Down 2 Command with Frequency Reference from Input Sources Other Than the Keypad
When a Run command is active and you release the Up/Down 2 command for longer than 5 s, the drive will save
the bias value in d4-06 [Frequency Ref Bias (Up/Down 2)]. The drive saves the frequency reference + d4-06 as a
frequency reference value. The drive will use the new value as the frequency reference when it restarts.
Figure 2.65 Up/Down 2 Example with Other Reference than Keypad and d4-01 = 1
Note:
To use the combination of the frequency reference hold function and the Up/Down 2 function, configure the Up/Down 2 upper limit [d4-08]
and lower limit [d4-09] correctly.
Remove the Saved Frequency Reference Value
The procedure to remove the saved frequency reference value is different for different functions. Use these methods
to remove the value:
Release the input programmed for Accel/Decel Ramp Hold [H1-xx = A].
Set an Up or Down command while no Run command is active.
Use the Up/Down 2 Command to set d4-06 = 0.0 or set d4-06 = 0.0 during stop.
d4-03: Up/Down 2 Bias Step Frequency
No.
(Hex.)
Name Description
Default
(Range)
d4-03
(02AA)
RUN
Up/Down 2 Bias Step
Frequency
Sets the bias that the Up/Down 2 function adds to or subtracts from the frequency reference.
0.00 Hz
(0.00 - 99.99 Hz)
The operation is different for different setting values:
Setting d4-03 = 0.00 Hz
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV