Parameter Details
2
2.7 F: Options
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 355
■ F7-65: PZD6 Write
No.
(Hex.)
Name Description
Default
(Range)
F7-65
(0785)
PZD6 Write
Sets the MEMOBUS/Modbus address for PZD6 (PPO output). A value of 0, 1, or 2 will disable the
PZD6 (PPO output) write operation to the MEMOBUS/Modbus register.
0
■ F7-66: PZD7 Write
No.
(Hex.)
Name Description
Default
(Range)
F7-66
(0786)
PZD7 Write
Sets the MEMOBUS/Modbus address for PZD7 (PPO output). A value of 0, 1, or 2 will disable the
PZD7 (PPO output) write operation to the MEMOBUS/Modbus register.
0
■ F7-67: PZD8 Write
No.
(Hex.)
Name Description
Default
(Range)
F7-67
(0787)
PZD8 Write
Sets the MEMOBUS/Modbus address for PZD8 (PPO output). A value of 0, 1, or 2 will disable the
PZD8 (PPO output) write operation to the MEMOBUS/Modbus register.
0
■ F7-68: PZD9 Write
No.
(Hex.)
Name Description
Default
(Range)
F7-68
(0788)
PZD9 Write
Sets the MEMOBUS/Modbus address for PZD9 (PPO output). A value of 0, 1, or 2 will disable the
PZD9 (PPO output) write operation to the MEMOBUS/Modbus register.
0
■ F7-69: PZD10 Write
No.
(Hex.)
Name Description
Default
(Range)
F7-69
(0789)
PZD10 Write
Sets the MEMOBUS/Modbus address for PZD10 (PPO output). A value of 0, 1, or 2 will disable the
PZD10 (PPO output) write operation to the MEMOBUS/Modbus register.
0
■ F7-70: PZD1 Read (Status Word)
No.
(Hex.)
Name Description
Default
(Range)
F7-70
(078A)
PZD1 Read (Status Word)
Sets the MEMOBUS/Modbus address for PZD1 (PPO Read). PZD1 (PPO input) functions as the
ZSW when F7-70 = 0.
0
■ F7-71: PZD2 Read (Output Frequency)
No.
(Hex.)
Name Description
Default
(Range)
F7-71
(078B)
PZD2 Read (Output
Frequency)
Sets the MEMOBUS/Modbus address for PZD2 (PPO Read). PZD2 (PPO input) functions as the
HIW when F7-71 = 0.
0
■ F7-72: PZD3 Read
No.
(Hex.)
Name Description
Default
(Range)
F7-72
(078C)
PZD3 Read
Sets the MEMOBUS/Modbus address for PZD3 (PPO Read). A value of 0 will disable the PZD3
(PPO Read) load operation from the MEMOBUS/Modbus register.
0