Parameter Details
2
2.8 H: Terminal Functions
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 401
■ 33: Zero Servo Complete
Setting Value Function Description
33 Zero Servo Complete
The terminal activates when positioning in the range set with b9-02 [Zero Servo Completion Window] completes after sending the
Zero-Servo command.
Note:
Refer to “b9: Zero Servo” for more information.
■ 37: During Frequency Output
Setting Value Function Description
37 During Frequency Output
The terminal activates when the drive outputs frequency.
ON : The drive outputs frequency.
OFF : The drive does not output frequency.
Note:
The terminal deactivates in these conditions:
• During Stop
• During baseblock
• During DC Injection Braking (initial excitation)
• During Short Circuit Braking
Figure 2.100 Active Frequency Output Time Chart
■ 38: Drive Enabled
Setting Value Function Description
38 Drive Enabled
This terminal activates when the H1-xx = 6A [Drive Enable] terminal activates.
■ 39: Watt Hour Pulse Output
Setting Value Function Description
39 Watt Hour Pulse Output
Outputs the pulse that shows the watt hours.
Note:
Refer to “H2-06: Watt Hour Output Unit Selection” for more information.
■ 3C: LOCAL Control Selected
Setting Value Function Description
3C LOCAL Control Selected
The terminal activates when the Run command source or frequency reference source is LOCAL.
ON : LOCAL
The keypad is the Run command source or the frequency reference source.
OFF : REMOTE