EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
644 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.8 H: Terminal Functions
412 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
H3-16: Terminal A1 Offset
No.
(Hex.)
Name Description
Default
(Range)
H3-16
(02F0)
Terminal A1 Offset
Sets the offset level for analog signals input to terminal A1. Usually it is not necessary to change this
setting.
0
(-500 - +500)
Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal of 0
V is input. For current input, this parameter will set the offset when a signal of 4 mA [H3-01= 2] or 0 mA [H3-01 = 3]
is input.
H3-17: Terminal A2 Offset
No.
(Hex.)
Name Description
Default
(Range)
H3-17
(02F1)
Terminal A2 Offset
Sets the offset level for analog signals input to terminal A2. Usually it is not necessary to change this
setting.
0
(-500 - +500)
Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal of 0
V is input. For current input, this parameter will set the offset when a signal of 4 mA [H3-09 = 2] or 0 mA [H3-09 =
3] is input.
H3-18: Terminal A3 Offset
No.
(Hex.)
Name Description
Default
(Range)
H3-18
(02F2)
Terminal A3 Offset
Sets the offset level for analog signals input to terminal A3. Usually it is not necessary to change this
setting.
0
(-500 - +500)
Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal of 0
V is input. For current input, this parameter will set the offset when a signal of 4 mA [H3-05 = 2] or 0 mA [H3-05 =
3] is input.
H3-40: Mbus Reg 15C1h Input Function
No.
(Hex.)
Name Description
Default
(Range)
H3-40
(0B5C)
Mbus Reg 15C1h Input
Function
Sets the MEMOBUS AI1 function.
F
(4 - 2F)
You can use the MFAI function from MEMOBUS/Modbus communications. Use this parameter to set the function.
Sets the input for the function in MEMOBUS/Modbus register 15C1.
Refer to H3-xx MFAI Setting Values for the setting values.
H3-41: Mbus Reg 15C2h Input Function
No.
(Hex.)
Name Description
Default
(Range)
H3-41
(0B5F)
Mbus Reg 15C2h Input
Function
Sets the MEMOBUS AI2 function.
F
(4 - 2F)
You can use the MFAI function from MEMOBUS/Modbus communications. Use this parameter to set the function.
Sets the input for the function in MEMOBUS/Modbus register 15C2.
Refer to H3-xx MFAI Setting Values for the setting values.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800

Related product manuals