Parameter Details
2
2.8 H: Terminal Functions
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 431
Figure 2.118 Virtual Digital I/O Functional Block Diagram
Note:
Refer to H1-xx "MFDI Setting Values" for more information on the virtual digital input setting values.
Refer to H2-xx "MFDO Setting Values" for more information on the virtual digital output setting values.
Refer to H3-xx "MFAI Setting Values" for more information on the virtual analog input setting values.
Refer to H4-xx "MFAO Setting Values" for more information on the virtual analog output setting values.
You cannot select 0 [3-Wire Sequence] or 20 to 2F [External Fault] in H7-01 to H7-04 [Virtual Multi-Function Input 1 to 4].
If the terminal is not used, set H7-01 to H7-04 = F. However, the through mode function is not supported.
The virtual I/O function selection and the multi-function input for DI-A3 cannot be used simultaneously.
H7-00: Virtual MFIO selection
No.
(Hex.)
Name Description
Default
(Range)
H7-00
(116F)
Expert
Virtual MFIO selection
Sets the function to enable and disable the virtual I/O function. Set this parameter to 1 to operate the
virtual I/O function.
0
(0, 1)
0 : Disabled
1 : Enabled
H7-01: Virtual Multi-Function Input 1
No.
(Hex.)
Name Description
Default
(Range)
H7-01
(1185)
Expert
Virtual Multi-Function Input
1
Sets the function that enters the virtual input set in H7-10 [Virtual Multi-Function Output 1].
F
(1 - 19F)
Note:
Settings 1B [Programming Lockout] and 11B [!Programming Lockout] are not available.
H7-02: Virtual Multi-Function Input 2
No.
(Hex.)
Name Description
Default
(Range)
H7-02
(1186)
Expert
Virtual Multi-Function Input
2
Sets the function that enters the virtual input set in H7-12 [Virtual Multi-Function Output 2].
F
(1 - 19F)
Note:
Settings 1B [Programming Lockout] and 11B [!Programming Lockout] are not available.
H7-03: Virtual Multi-Function Input 3
No.
(Hex.)
Name Description
Default
(Range)
H7-03
(1187)
Expert
Virtual Multi-Function Input
3
Sets the function that enters the virtual input set in H7-14 [Virtual Multi-Function Output 3].
F
(1 - 19F)
Note:
Settings 1B [Programming Lockout] and 11B [!Programming Lockout] are not available.
H7-01
[Virtual Multi-Function
Input 1]
H7-11
[Virtual Output
1 Delay Time]
H7-10
[Virtual Multi-Function
Output 1]
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV