Parameter Details
2
2.9 L: Protection Functions
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 471
1 : oL5 @ Speed > L6-09 - Alarm
When the speed (signed) L6-09 [Mech Fatigue Detect Speed Level], the drive detects mechanical weakening. The
drive will detect oL5 [Mechanical Weakening Detection 1] and continue operation.
2 : oL5 @ lSpeedl > L6-09 - Alarm
When the speed (absolute value) L6-09, the drive detects mechanical weakening. The drive will detect oL5 and
continue operation.
3 : oL5 @ Speed > L6-09 - Fault
When the speed (signed) L6-09, the drive detects mechanical weakening. The drive will detect oL5 and stop
operation.
4 : oL5 @ lSpeedl > L6-09 - Fault
When the speed (absolute value) L6-09, the drive detects mechanical weakening. The drive will detect oL5 and stop
operation.
5 : UL5 @ Speed < L6-09 - Alarm
When the speed (signed) L6-09, the drive detects mechanical weakening. The drive will detect UL5 [Mechanical
Weakening Detection 2] and continue operation.
6 : UL5 @ lSpeedl < L6-09 - Alarm
When the speed (absolute value) L6-09, the drive detects mechanical weakening. The drive will detect UL5 and
continue operation.
7 : UL5 @ Speed < L6-09 - Fault
When the speed (signed) L6-09, the drive detects mechanical weakening. The drive will detect UL5 and stop
operation.
8 : UL5 @ lSpeedl < L6-09 - Fault
When the speed (absolute value) L6-09, the drive detects mechanical weakening. The drive will detect UL5 and stop
operation.
L6-09: Mech Fatigue Detect Speed Level
No.
(Hex.)
Name Description
Default
(Range)
L6-09
(0469)
Mech Fatigue Detect Speed
Level
Sets the speed level where the drive will operate the mechanical deterioration detection function, as a
percentage of the Maximum Output Frequency.
110.0%
(-110.0 - 110.0%)
Parameters L6-01 to L6-03 [Torque Detection 1 Settings Parameters] set the overtorque/undertorque detection
conditions.
When L6-08 = 2, 4, 6, 8 [Mechanical Fatigue Detect Select = Speed : unsigned], the setting value of L6-09 is the
absolute value. When L6-09 is set to a negative number, the drive processes this value as a positive number.
L6-10: Mech Fatigue Detect Delay Time
No.
(Hex.)
Name Description
Default
(Range)
L6-10
(046A)
Mech Fatigue Detect Delay
Time
Sets the time for mechanical deterioration detection.
0.1 s
(0.0 - 10.0 s)
When the detection conditions set in L6-08 [Mechanical Weakening Detect Ope] continue for the time set in L6-10,
the drive will detect mechanical weakening.
L6-11: Mech Fatigue Hold Off Time
No.
(Hex.)
Name Description
Default
(Range)
L6-11
(046B)
Mech Fatigue Hold Off Time
Sets the time that the drive will start mechanical deterioration detection triggered by the cumulative
operation time of the drive.
0 h
(0 - 65535 h)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV