2.9 L: Protection Functions
482 YASKAWA TOEPYAIGA8002B GA800 Drive Programming
L8-54: STPo Id Diff Detection
No.
(Hex.)
Name Description
Default
(Range)
L8-54
(0474)
Expert
STPo Id Diff Detection
Sets the Id deviation detection function for STPo [Motor Step-Out Detected].
1
(0, 1)
0 : Disabled
1 : Enabled
L8-55: Internal DB TransistorProtection
No.
(Hex.)
Name Description
Default
(Range)
L8-55
(045F)
Internal DB
TransistorProtection
Sets the protection function for the internal braking transistor.
1
(0, 1)
0 : Disable
Disables braking transistor protection.
Use this setting, if enabling the braking transistor can cause an rF [Braking Resistor Fault] in these conditions:
With a regenerative converter, for example D1000.
With a regenerative unit, for example R1000.
When connecting braking resistor options to the drive, for example CDBR units.
Without an internal braking transistor.
1 : Protection Enabled
Prevents damage to the internal braking transistor when using a braking transistor or optional braking resistors.
These models have a built-in braking transistor:
2004 to 2138
4002 to 4168
L8-56: Stall P @ Accel Activation Time
No.
(Hex.)
Name Description
Default
(Range)
L8-56
(047D)
Expert
Stall P @ Accel Activation
Time
Sets the length time that the acceleration stall prevention function can continue to operate before the
drive detects an STPo [Motor Step-Out Detected].
5000 ms
(100 - 5000 ms)
Note:
If this value is too small, it can cause incorrect detection of STPo. If this value is too large, the drive will not detect STPo.
L8-57: Stall Prevention Retry Counts
No.
(Hex.)
Name Description
Default
(Range)
L8-57
(047E)
Expert
Stall Prevention Retry
Counts
Sets the number of times the acceleration stall prevention function can operate until speeds agree
before the drive detects an STPo [Motor Step-Out Detected].
10
(1 - 10 times)
Note:
If this value is too small, it can cause incorrect detection of STPo. If this value is too large, the drive will not detect STPo.
L8-90: STPo Detection Level (Low Speed)
No.
(Hex.)
Name Description
Default
(Range)
L8-90
(0175)
Expert
STPo Detection Level (Low
Speed)
Sets the detection level that the control fault must be equal to or more than to cause an STPo [Motor
Step-Out Detected].
Determined by A1-02
(0 - 5000 times)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV