Parameter Details
2
2.11 o: Keypad-Related Settings
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 519
2 : Clear all
Deletes all of the saved user parameter setting values.
Set o2-03 = 2 then push to clear the user parameter setting values. The drive will automatically reset o2-03 to 0. If
you delete the user parameter setting values, you cannot set A1-03 = 1110 to initialize parameters.
■ o2-04: Drive Model (KVA) Selection
No.
(Hex.)
Name Description
Default
(Range)
o2-04
(0508)
Drive Model (KVA)
Selection
Sets the Drive Model code. Set this parameter after replacing the control board.
Determined by the drive
(-)
NOTICE: Set o2-04 [Drive Model Selection] correctly. If you set this parameter incorrectly, it will decrease drive performance, cause
the protection function to operate incorrectly, and cause damage to the drive.
Note:
When the setting value of o2-04 changes, related parameter setting values also change. Refer to Defaults by Drive Model and Duty Rating
ND/HD on page 133 for more information.
These tables list the relation between o2-04 setting values and drive models.
o2-04 Setting Drive Model
62 2004
63 2006
64 2008
65 2010
66 2012
67 2018
68 2021
6A 2030
6B 2042
6D 2056
6E 2070
6F 2082
70 2110
72 2138
73 2169
74 2211
75 2257
76 2313
77 2360
78 2415
92 4002
93 4004
94 4005
o2-04 Setting Drive Model
95 4007
96 4009
97 4012
99 4018
9A 4023
9C 4031
9D 4038
9E 4044
9F 4060
A1 4075
A2 4089
A3 4103
A4 4140
A5 4168
A6 4208
A7 4250
A8 4302
A9 4371
AA 4414
AC 4477
AD 4568
AE 4605
AF 4720