EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
644 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
2
2.11 o: Keypad-Related Settings
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 525
Note:
The maintenance period changes for different operating environments.
o4-11: Fault Trace/History Init (U2/U3)
No.
(Hex.)
Name Description
Default
(Range)
o4-11
(0510)
Fault Trace/History Init (U2/
U3)
Resets the records of Monitors U2-xx [Fault Trace] and U3-xx [Fault History].
0
(0, 1)
Note:
When you initialize the drive with A1-03 [Initialize Parameters], the drive will not reset the records for U2-xx and U3-xx.
0 : Disabled
Keeps the records of Monitors U2-xx and U3-xx.
1 : Enabled
Resets the records for Monitors U2-xx and U3-xx. After the reset, the drive automatically resets o4-11 to 0.
o4-12: kWh Monitor Initialization
No.
(Hex.)
Name Description
Default
(Range)
o4-12
(0512)
kWh Monitor Initialization
Resets the monitor values for U4-10 [kWh, Lower 4 Digits] and U4-11 [kWh, Upper 5 Digits].
0
(0, 1)
Note:
When you initialize the drive with A1-03 [Initialize Parameters], the drive will not reset U4-10 and U4-11.
0 : No Reset
Keeps the monitor values for U4-10 and U4-11.
1 : Reset
Resets the values of U4-10 and U4-11. After the reset, the drive automatically resets o4-12 to 0.
o4-13: RUN Command Counter @ Initialize
No.
(Hex.)
Name Description
Default
(Range)
o4-13
(0528)
RUN Command Counter @
Initialize
Resets the monitor values for U4-02 [Num of Run Commands], U4-24 [Number of Runs (Low)], and
U4-25 [Number of Runs (High)].
0
(0, 1)
0 : No Reset
Keeps the monitor values for U4-02, U4-24, and U4-25.
1 : Reset
Resets the values of U4-02, U4-24, and U4-25. After the reset, the drive automatically resets o4-13 to 0.
o4-22: Time Format
No.
(Hex.)
Name Description
Default
(Range)
o4-22
(154F)
RUN
Time Format
Sets the time display format. This parameter is only available when using an LCD keypad.
1
(0 - 2)
Sets the display of the time shown in the upper-left of the LCD keypad screen.
0 : 24 Hour Clock
1 : 12 Hour Clock
2 : 12 Hour JP Clock
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents