No.
(Addr.
Hex)
Name LCD Display Description Values Page
F6-58
(03D9)
DeviceNet Torque
Scaling
Torque Scale
Sets the scaling factor for the torque monitor in DeviceNet. Default: 0
Min.: -15
Max.: 15
–
F6-59
(03DA)
DeviceNet Power
Scaling
Power Scale
Sets the scaling factor for the power monitor in DeviceNet. Default: 0
Min.: -15
Max.: 15
–
F6-60
(03DB)
DeviceNet Voltage
Scaling
Voltage Scale
Sets the scaling factor for the voltage monitor in DeviceNet. Default: 0
Min.: -15
Max.: 15
–
F6-61
(03DC)
DeviceNet Time
Scaling
Time Scale
Sets the scaling factor for the time monitor in DeviceNet. Default: 0
Min.: -15
Max.: 15
–
F6-62
(03DD)
DeviceNet Heartbeat
Interval
DN Heart Beat
Sets the heartbeat interval for DeviceNet communications. Default: 0
Min.: 0
Max.: 10
–
F6-63
(03DE)
DeviceNet Network
MAC ID
DN MAC ID MEM
Saves and monitors settings 0 to 63 of F6-50 (DeviceNet MAC
Address).
Default: 63
Min.: 0
Max.: 63
–
F6-64 to
F6-71
(03DF to
03C8)
Reserved –
Dynamic I/O Assembly Parameters
– –
F6-72
(03DE)
PowerLink Node
Address
PowerLink NodeID Reserved. – –
F7-01
(03E5)
<4>
IP Address 1
IP Address 1
Sets the most significant octet of network static IP address.
Default: 192
Range: 0 to 255
–
F7-02
(03E6)
<4>
IP Address 2
IP Address 2
Sets the second most significant octet of network static IP
address.
Default: 168
Range: 0 to 255
–
F7-03
(03E7)
<4>
IP Address 3
IP Address 3
Sets the third most significant octet of network static IP address.
Default: 1
Range: 0 to 255
–
F7-04
(03E8)
<4>
IP Address 4
IP Address 4
Sets the fourth most significant octet of network static IP
address.
Default: 20
Range: 0 to 255
–
F7-05
(03E9)
Subnet Mask 1 Subnet Mask 1 Sets the most significant octet of network static Subnet Mask.
Default: 255
Range: 0 to 255
–
F7-06
(03EA)
Subnet Mask 2 Subnet Mask 2
Sets the second most significant octet of network static Subnet
Mask.
Default: 255
Range: 0 to 255
–
F7-07
(03EB)
Subnet Mask 3 Subnet Mask 3
Sets the third most significant octet of network static Subnet
Mask.
Default: 255
Range: 0 to 255
–
F7-08
(03EC)
Subnet Mask 4 Subnet Mask 4
Sets the fourth most significant octet of network static Subnet
Mask.
Default: 0
Range: 0 to 255
–
F7-09
(03ED)
Gateway Address 1 Gateway IP Add 1 Sets the most significant octet of network Gateway address.
Default: 192
Range: 0 to 255
–
F7-10
(03EE)
Gateway Address 2 Gateway IP Add 2
Sets the second most significant octet of network Gateway
address.
Default: 168
Range: 0 to 255
–
F7-11
(03EF)
Gateway Address 3 Gateway IP Add 3
Sets the third most significant octet of network Gateway
address.
Default: 1
Range: 0 to 255
–
F7-12
(03E0)
Gateway Address 4 Gateway IP Add 4
Sets the fourth most significant octet of network Gateway
address.
Default: 1
Range: 0 to 255
–
F7-13
(03F1)
Address Mode at Startup
IP Add Mode Sel
0: User Defined
1: BOOTP
2: DHCP
Select the option address setting method
0: Static
<5>
1: BOOTP
2: DHCP
Default: 2
Range: 0 to 2
–
F7-14
(03F2)
Duplex Mode Selection
Duplex Select
0: Half Duplex
1: Auto Negotiate
2: Full Duplex
Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced
Default: 1
Range: 0 to 2
–
B.7 F: Options
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
371
B
Parameter List