4.4
SVA-01 Module Parameter Details
4-81
( 25 ) Filters
OW
3A
S-curve Acceleration Time
Setting Range Setting Unit Default Value
0 to 65535 0.1 ms 0
Sets the acceleration/deceleration filter time constant.
Always verify that pulse distribution has been completed (monitoring parameter IB
0C0 is ON) before changing the time
constant.
After setting the filter type to be used, change the time constant.
Once the filter type is set, the setting is held until the power is turned OFF or the filter type is changed.
There are two types of acceleration/deceleration filter: an exponential acceleration/deceleration filter and a moving average
filter.
The following table shows the relationship with related parameters.
OW
3B
Bias Speed for Exponential
Acceleration/Deceleration
Filter
Setting Range Setting Unit Default Value
0 to 32767
Speed Units (setting parameter
OW
03, bits 0 to 3)
0
Set the bias speed for exponential acceleration/deceleration with bias.
Position
Phase
Speed
Torque
OW3A
OW3A
Step input
No filter
Acceleration/deceleration used
OW36
OW3A
OW3A
OW38
OW36
OW38
OW03, bits 8 to B = 0
Exponential Acceleration/
Deceleration Filter
OW03, bits 8 to B = 1
Moving Average Filter
OW03, bits 8 to B = 2
Position
Phase
Speed
Torque