EasyManuals Logo

YASKAWA Varispeed L7 User Manual

YASKAWA Varispeed L7
243 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #113 background imageLoading...
Page #113 background image
4-46
S1-14
SE2 detec-
tion delay
time
Used to set the time to detect
SE2 fault in units of 1ms.
When the inverter output cur-
rent is below S1-08 setting
after passing S1-06+S1-14
time,SE2 will be detected.
0
to
S1-04 -
S1-06
200ms No A A A 6A1H -
SE2 det T
S1-15
SE3 detec-
tion delay
time
Used to set the time to detect
SE3 fault in units of 1ms.
When Inverter output currnet
is below S1-08 setting for S1-
15 time continuously, SE3 will
be detected.
0
to
5000
200ms No A A A 6A2H -
SE3 det T
S1-16
RUN delay
time Used to set RUN-delay time in
unit of 1 second
0.00
to
1.00
0.10sec No A A A 6A3H -
Run Delay T
S1-17
DC injection
current gain
at regenera-
tion
Used to set the DC injection
gain when inveter is in the
regerenative mode.
0
to
400
100% No No A No 6A4H -
DC Inj
gain@gen
S1-18
DC injection
current gain
at motoring
Used to set the DC injection
gain when inveter is in the
motoring mode.
0
to
400
20% No No A No 6A5H -
DC Inj
gain@mot
S1-19
Output con-
tactor open
delay time
Used to set the delay time to
close the output contactor in
units of 1 second.
0.00
to
1.00
0.10sec No A A A 6A6H -
Cont open
delay
S1-20
Zero-servo
gain
Adjust the strength of the zero-
servo lock.
When the closed loop vector
control is selected, a position
control loop is created and the
motor stops at start or stop.
Increasing the zero-servo gain
in turn increases the strength of
the lock. Increasing it by too
much will cause oscillation.
0 to 100 5 No No No A 6A7H -
Zero Servo
Gain
S1-21
Zero-servo
completion
width
Sets the output width of the P-
lock completion signal.
The zero-servo completion sig-
nal is ON when the current
position is within the range
(the zero-servo position +
zero-servo completion width.)
Set the allowable position dis-
placement from the zero-servo
position to 4 times the pulse
rate of the PG (pulse generator,
encoder) in use.
0 to
16383
10 No No No A 6A8H -
Zero Servo
Count
S1-22
Torque com-
pensation
time at start
Sets the time to torque refer-
ence to reach to 300% torque
reference in units of 1ms.
0
to
5000
500ms No No No A 6A9H -
Torque incr T
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
Open
Loop
Vector
Closed
Loop
Vector
Display
http://nicontrols.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed L7 and is the answer not in the manual?

YASKAWA Varispeed L7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed L7
CategoryInverter
LanguageEnglish

Related product manuals