EasyManua.ls Logo

YASKAWA Varispeed L7 - Page 118

YASKAWA Varispeed L7
243 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Parameter Tables
4-51
4
Param-
eter
Number
Name
Description
Output Signal Level
During Multi-Function
Analog Output
Min.
Unit
Control Methods MEMO-
BUS
Regis-
ter
V/f
Open
Loop
Vector
Closed
Loop
Vector
Display
U1-10
Input termi-
nal status
Shows input ON/OFF status.
(Cannot be output.) - A A A 49H
Input Term
Sts
U1-11
Output termi-
nal status
Shows output ON/OFF status.
(Cannot be output.) - A A A 4AH
Output Term
Sts
U1-12
Operation
status
Inverter operating status.
(Cannot be output.) - A A A 4BH
Int Ctl Sts 1
U1-13
Cumulative
operation
time
Monitors the total operating
time of the Inverter.
The initial value and the oper-
ating time/power ON time
selection can be set in o2-07
and o2-08.
(Cannot be output.)
1
hr
AA A 4CH
Elapsed Time
U1-14
Software No.
(flash mem-
ory)
(Manufacturer’s ID number) (Cannot be output.) - A A A 4DH
FLASH ID
U1-15
Terminal A1
input level
Monitors the input level of
analog input A1. A value of
100% corresponds to 10V
input.
10 V: 100%
(0 to ± 10 V possible)
0.1% A A A 4EH
Term A1
Level
1: FWD comman
d
(S1) is ON
1: REV command
(S2) is ON
1: Multi input 1
(S3) is ON
1: Multi input 2
(S4) is ON
1: Multi input 3
(S5) is ON
1: Multi input 4
(S6) is ON
1: Multi input 5
(S7) is ON
1: Multi-function
contact output 1
(M1-M2) is ON
1: Multi-function
contact output 2
(M3-M4) is ON
1: Multi-function
contact output 3
(M5-M6) is ON
Not used
(Always 0).
1: Error output
(MA/MB-MC) is
ON
Run
1: Zero speed
1: Reverse
1: Reset signal
input
1: Speed agree
1: Inverter ready
1: Minor fault
1: Major fault
http://nicontrols.com