EasyManua.ls Logo

YASKAWA Varispeed L7 - Page 92

YASKAWA Varispeed L7
243 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Parameter Tables
4-25
4
Analog Monitor Cards: F4
User constants for the Analog Monitor Card are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
Display
V/f
Open
Loop
Vec-
tor
Closed
Loop
Vector
F4-01
Channel 1
monitor
selection
Effective when the Analog
Monitor Card is used.
Monitor selection:
Set the number of the monitor
item to be output. (U1-)
Gain:
Set the multiple of 10 V for
outputting monitor items.
4, 10 to 14, 25, 28, 34, 39, 40
cannot be set. 29 to 31 and 41
are not used. When the AO-
12 Analog Monitor Card is
used, outputs of ± 10 V are
possible. To output ± 10 V, set
F4-07 or F4-08 to 1. When
the AO-08 Analog Monitor
Card is used, only outputs of
0 to +10 V are possible.
A meter calibration function
is available.
1 to 99 2 No A A A 391H
-
AO Ch1
Select
F4-02
Channel 1
gain
0.0 to
1000.0
100.0% Yes A A A 392H
-
AO Ch1 Gain
F4-03
Channel 2
monitor
selection
1 to 99 3 No A A A 393H
-
AO Ch2
Select
F4-04
Channel 2
gain
0.0 to
1000.0
50.0% Yes A A A 394H
-
AO Ch2 Gain
F4-05
Channel 1
output moni-
tor bias
Sets the channel 1 item bias
to 100%/10 V when the ana-
log monitor card is used.
-110.0
to
110.0
0.0% Yes A A A 395H
-
AO Ch1 Bias
F4-06
Channel 2
output moni-
tor bias
Sets the channel 2 item bias
to 100%/10 V when the ana-
log monitor card is used.
-110.0
to
110.0
0.0% Yes A A A 396H
-
AO Ch2 Bias
F4-07
Analog out-
put signal
level for
channel 1
0: 0 to 10 V
1: -10 to +10 V
0 or 1 0 No A A A 397H -
AO Opt
Level Sel
F4-08
Analog out-
put signal
level for
channel 2
0: 0 to 10 V
1: -10 to +10 V
0 or 1 0 No A A A 398H
-
AO Opt
Level Sel