6-23
IM 04L20A01-01E
Operations for Changing the Displayed Contents
6
Setup Items
Detailed Setting of the Partial Expanded Display
• First-CH/Last-CH
Set the target channel (common with the [Zone] and [Graph] settings).
Measurement channels: 01 to 12, computation channels: 31 to 42 (/M1, /PM1 option)
• Partial
To use partial expanded display, select [On] (initial value is [Off]). If [On] is selected,
the [Expand] and [Boundary] entry boxes appear.
• Expand
Set the position where the boundary value is to be displayed within the display
span in the range of [1] to [99]%.
• Boundary
Set the value that is to be the boundary between the reduced section and the
expanded section in the range of “minimum span value + 1 digit to maximum span
value − 1 digit.” However, for channels that are set to scaling or square root
computation, the selectable range is “minimum scale value + 1 digit to maximum
scale value − 1 digit.”
Example
Suppose [Expand] and [Boundary] are set to 30 and 0, respectively, for a channel
with “−6 V to 6 V” measurement span.
The measured data for “−6 V–0 V” and “0 V–6 V” are displayed in the “0%–30%”
and “70%–100%” ranges, respectively.
Note
If the range setting of a channel is set to [Skip] or if the span width is less than 1 digit, partial
expanded display cannot be used (the [Partial] box is grayed).
6.12 Displaying Partially Expanded Waveforms