8-13
IM 04L20A01-01E
Computation and Report Function Related Operations (/M1 or /PM1 Option)
8
Number of samples
Set the average count when taking the moving average using an integer between [1]
and [250].
Note
If the number of data points to be averaged has not reached the specified number of samples
immediately after computation is started, the average of the available data is calculated.
Computation error data is excluded from the rolling average computation.
If the computed data exceeds the upper or lower limit, the data is clipped at the upper or
lower limit, and the rolling average is computed. The upper and lower limit is “±100000000"
excluding the decimal point. The decimal point position is the same as that of the span lower
limit.
8.5 Setting the Rolling Average