10-6 IM 04L20A01-01E
Code Message
285 FTP data connection error.
Further details are provided by the character string that appears after error code 285.
Character String and Details
SOCKET
Failed to create a socket for the transfer connection.*
3
BIND
Failed the transfer connection command.*
3
CONNECT
Failed the transfer connection.*
3
LISTEN
Failed the transfer connection reception.*
3
ACCEPT
Failed to accept the transfer connection.*
3
SOCKNAME
Internal processing error.*
2
RECV
Failed to receive data over the transfer connection.*
3
SEND
Failed to send data over the transfer connection.*
3
286 FTP file transfer error.
Further details are provided by the character string that appears after error code 286.
Character String and Details
READ
Internal processing error.*
2
WRITE
Internal processing error.*
2
*1 See the “
FX100 Communication Interface User’s Manual
”
(IM 04L20A01-17E).
*2 Contact your nearest YOKOGAWA dealer.
*3 These errors may occur if the network experiences trouble during the data transmission (bad
cable connection, duplicate addresses, network equipment failure).
Note
• The FTP client function on the FX100 has a timer function that drops the connection if there is
no data transfer for two minutes. If the server does not respond within this time period, the
transfer fails.
• The FTP client function on the FX100 overwrites files with the same file names on the server
without any warnings, unless the server rejects the request.
• For information regarding the FTP client function of the FX100, see the “
FX100
Communication Interface User’s Manual
”
(IM 04L20A01-17E).
Communication Errors
For information regarding the communication function of the FX100, see the “
FX100
Communication Interface User’s Manual
”
(IM 04L20A01-17E).
•Errors during Setting and Basic Setting Modes, Output Communication Command
Execution, and Setup Data Loading
Code Message
300 Command is too long.
301 Too many number of commands delimited with ‘;’.
302 This command has not been defined.
303 Data request command can not be enumerated with sub-delimiter.
350 Command is not permitted to the current user level.
351 This command cannot be specified in the current mode.
352 The option is not installed.
353 This command cannot be specified in the current setting.
354 This command is not available during sampling or calculating.
10.1 A List of Messages