Appendix A Troubleshooting EDS File
226 9ARD000014-600 A
9 IO files can be
imported only along
with corresponding
adapter files!
Import has been
started with IO EDS
file instead of
adapter EDS file in
case of Modular IO
Modular
EtherNet/IP/
DeviceNet
Import will abort.
Start the import with
an adapter EDS file in
case of Modular IO.
10 The wizard cannot
proceed as the file
is not as per CIP
specifications.
There are required
fields in the File
section that are
missing. Please
restart the wizard
with the correct
EDS file.
Any of the
mandatory fields in
File Section
required in EDS file
is missing or fields
available as not as
per CIP
specifications
(example: create
date, create time
etc.)
EtherNet/IP/
DeviceNet
Import will abort.
Contact the vendor to
get device EDS files
with all the mandatory
fields.
11 The wizard cannot
proceed as the file
is not as per CIP
specifications.
There are required
fields in the
Device section that
are missing. Please
restart the wizard
with the correct
EDS file.
Any of the
mandatory fields in
Device Section
required in EDS file
is missing or fields
available as not as
per CIP
specifications
(example: vendor
code, product code
etc.)
EtherNet/IP/
DeviceNet
Import will abort.
Contact the vendor to
get device EDS files
with all the mandatory
fields.
Table 41. Messages - Import of EDS Files (Continued)
Sl
No
Message Reason
Applicability
Based on Device
Classification
Additional
Information and
Workaround