Appendix A Troubleshooting EDS File
9ARD000014-600 A 235
44 Invalid member
size in assembly
section. Do you
want to continue?
Member size field
has invalid entry in
assem section of
EDS file
Modular
EtherNet/IP/
DeviceNet
Continue the import
with this message.
Else, import will be
aborted and contact
the vendor to get
device EDS files with
all the valid entries.
45 Invalid Switch
selector, in
variants. Do you
want to continue?
Switch selector field
in variants section
of EDS file has
invalid entry
General Purpose
Device
EtherNet/IP/
DeviceNet
Continue the import
with this message.
Else, import will be
aborted and contact
the vendor to get
device EDS files with
all the valid entries.
46 Invalid selection
entry, in variants.
Do you want to
continue?
Selection entry is
invalid in variants
section of EDS file.
General Purpose
Device
EtherNet/IP/
DeviceNet
Continue the import
with this message.
Else, import will be
aborted and contact
the vendor to get
device EDS files with
all the valid entries.
47 Invalid IO mask, in
IO section. Do you
want to continue?
IO mask field has
an invalid entry in
IO section of EDS
file
DeviceNet Continue the import
with this message.
Else, import will be
aborted and contact
the vendor to get
device EDS files with
all the valid entries.
Table 41. Messages - Import of EDS Files (Continued)
Sl
No
Message Reason
Applicability
Based on Device
Classification
Additional
Information and
Workaround