Connection Error Appendix B Troubleshooting CI873 Log Entries
248 9ARD000014-600 A
4 Connection not found
at target
application
Data sent to slave device for a
connection that is not available in
the slave device. Try closing the
existing connection and establish a
new connection.
EtherNet/IP
5 Invalid connection
type or connection
priority
Connection type (point to point,
multicast) and connection priority
(schedule, High, Low) used in the
connection request is not supported
by the device. Check the EDS file for
correctness.
EtherNet/IP/DeviceNet
6 Invalid connection
size
Either the O->T or T-> size specified
in the control builder configuration
does not match the size in the
physical device. Check the
correctness of the EDS file.
EtherNet/IP/DeviceNet
7 RPI not supported or
there is a problem
with connection
time-out multiplier
or production
inhibit time
Check the EDS file for the
correctness.
EtherNet/IP
8 Connection Manager
cannot support any
more connections
All the connections of the slave
device have been utilized. No more
connections available.
EtherNet/IP
9 Either the Vendor Id
or the Product Code
in the key segment
did not match the
device
Check the correctness of the EDS
file. Ensure that the device used in
the control builder configuration is
same as the physical device.
EtherNet/IP/DeviceNet
Table 42. Connection Errors (Continued)
Sl
No
Message in CI873 Log Description
Applicability based on
device classification