Appendix B Troubleshooting CI873 Log Entries Connection Error
9ARD000014-600 A 249
10 Product Type in the
key segment did not
match the device
Check the correctness of the EDS
file. Ensure that the device used in
the control builder configuration is
same as the physical device.
EtherNet/IP/DeviceNet
11 Major or Minor
revision information
in the key segment
did not match the
device
Check the correctness of the EDS
file. Ensure that the device used in
the control builder configuration is
same as the physical device.
EtherNet/IP/DeviceNet
12 Invalid connection
point specified in
the connection path
Check the EDS file for the
correctness. Connection point used
does not match with the physical
device.
EtherNet/IP
13 Invalid
configuration format
Ensure that the right device is
configured in the control builder.
Check the EDS file for the
correctness.
EtherNet/IP
14 Connection request
fails since there is
no controlling
connection currently
open
For listen only connection there
should be an exclusive owner
connection originated to the slave
device.
EtherNet/IP
15 Target application
cannot support any
more connections
All the connection resources in the
slave device are exhausted. Try
closing certain connections and
retry.
EtherNet/IP
16 RPI is smaller than
the Production
Inhibit time
Check the EDS file for the
correctness.
EtherNet/IP
Table 42. Connection Errors (Continued)
Sl
No
Message in CI873 Log Description
Applicability based on
device classification