Appendix B Troubleshooting CI873 Log Entries Configuration Error
9ARD000014-600 A 253
6 The messaging
connection was lost
Connection used to send the
Tag data to PLC is
disconnected for some reason.
Ensure that the PLC is
available in the network.
EtherNet/IP
7 The requested service
was not implemented or
was not defined for
this object
class/instance
Certain information in EDS file
does not match with the slave
device configuration. Ensure
that the right EDS file for the
device is used. Check the
Major and minor version of the
EDS file.
EtherNet/IP/DeviceNet
8 Invalid attribute data
detected
Value sent in the configuration
request is invalid. Check the
correctness of the EDS file.
EtherNet/IP/DeviceNet
9 The object is already
in the mode/state
being requested by the
service
While trying to change the
state of the device say from
Idle to Run or Run to idle
check if the device is already in
that required state.
EtherNet/IP/DeviceNet
10 A request to modify a
non-modifiable
attribute was received
EtherNet/IP/DeviceNet
11 The device's current
mode/state prohibits
the execution of the
requested service
Configuration of certain
parameters are not allowed
when the device is in run or
connected state. Ensure that
the device is in right state.
EtherNet/IP/DeviceNet
Table 43. Configuration Error (Continued)
Sl
No
Message in CI873 Log Description
Applicability based on
device classification