Parameters 115
05.20 Diagnostic word 1 Diagnostic word 1. For possible causes and remedies,
see chapter Fault tracing.
0b0000
0b0000…0b1111 Diagnostic word 1. 1 = 1
05.21 Diagnostic word 2 Diagnostic word 2. For possible causes and remedies,
see chapter Fault tracing.
0b0000
0b0000…0b1111 Diagnostic word 2. 1 = 1
05.22 Diagnostic word 3 Diagnostic word 3. For possible causes and remedies,
see chapter Fault tracing.
0b0000
0b0000…0b1111 Diagnostic word 3. 1 = 1
05.80 Motor speed at fault Displays the motor speed (01.01) at which fault occurred. -
-30000.00…
30000.00 rpm
Motor speed at fault. See par.
46.01
05.81 Output frequency at
fault
Displays the output frequency (01.06) at which fault
occurred.
-
-500.00…500.00 Hz Output frequency at fault. See par.
46.02
05.82 DC voltage at fault Displays the DC link volt age (01.11) at which fault
occurred.
-
0.00…2000.00 V DC voltage at fault. 10 = 1 V
No. Name/Value Description Default
FbEq 16
Bit Name Value
0 Any warning or fault Yes = Drive has generated a warning or tripped on a fault.
1 Any warning Yes = Drive has generated a warning.
2 Any fault Yes = Drive has tripped on a fault.
3 Reserved
4 Overcurrent fault Yes = Drive has tripped on fault 2310 Overcurrent.
5 Reserved
6 DC overvoltage Yes = Drive has tripped on fault 3210 DC link overvoltage.
7 DC undervoltage Yes = Drive has tripped on fault 3220 DC link undervoltage.
8 Reserved
9 Device overtemp flt Yes = Drive has tripped on fault 4310 Excess temperature.
10...15 Reserved
Bit Name Value
0...9 Reserved
10 Motor overtemp flt Yes = Drive has tripped on fault 4981 External
temperature 1.
11…15 Reserved
Bit Name Value
0...8 Reserved
9 kWh pulse 1 = kWh pulse is active.
10 Reserved
11 Fan command 1 = Drive fan is rotating above idle speed.
12…15 Reserved