Parameters 143
In1P Start; In2 Stop The sources of the start and stop commands are selected
by parameters 20.03 Ext1 in1 source and 20.04 Ext1 in2
source. The state transitions of the source bits are
interpreted as follows:
Notes:
Parameter 20.02 Ext1 start trigger type has no effect
with this setting.
When source 2 is 0, the Start and Stop keys on the
control panel are disabled.
4
In1P Start; In2 Stop;
In3 Dir
The sources of the start and stop commands are selected
by parameters 20.03 Ext1 in1 source and 20.04 Ext1 in2
source. The source selected by 20.05 Ext1 in3 source
determines the direction. The state transitions of the
source bits are interpreted as follows:
Notes:
Parameter 20.02 Ext1 start trigger type has no effect
with this setting.
When source 2 is 0, the Start and Stop keys on the
control panel are disabled.
5
In1P Start fwd; In2P
Start rev; In3 Stop
The sources of the start and stop commands are selected
by parameters 20.03 Ext1 in1 source, 20.04 Ext1 in2
source and 20.05 Ext1 in3 source. The source selected by
20.05 Ext1 in3 source determines the direction. The state
transitions of the source bits are interpreted as follows:
Note: Parameter 20.02 Ext1 start trigger type has no
effect with this setting.
6
Control panel Start; stop and direction commands through control panel;
when EXT1 is active. Applies also for PC-Tool when it is
connected via panel port.
11
Embedded fieldbus The start and stop commands are taken from the
embedded fieldbus interface.
Note: The start signal is always level-triggered with this
setting regardless of parameter 20.02 Ext1 start trigger
type.
14
No. Name/Value Description Default
FbEq 16
State of source 1
(20.03)
State of source 2
(20.04)
Command
0
-
> 1 1 Start
Any 0 Stop
State of
source 1
(20.03)
State of
source 2
(20.04)
State of
source 3
(20.05)
Command
0
-
> 1 1 0 Start forward
0
-
> 1 1 1 Start reverse
Any 0 Any Stop
State of
source 1
(20.03)
State of
source 2
(20.04)
State of
source 3
(20.05)
Command
0
-
> 1 Any 1 Start forward
Any 0
-
> 1 1 Start reverse
Any Any 0 Stop
ACS180 FW.book Page 143 Tuesday, March 9, 2021 2:25 PM